in comparison to the change in the load current. The
End
section 2
setting allows for CT
errors.
In section 3, where I
b
/I
n
>
End section 2
, the slope of the characteristic is constant.
The slope is 100 percent, which means that an increase in the differential current is equal
to the corresponding increase in the stabilizing current.
The required differential current for tripping at a certain stabilizing current level can be
calculated using the formulae:
For a stabilizing current lower than
End section 1
Equation 29
For a stabilizing current higher than
End section 1
but lower than
End section 2
Equation 30
For higher stabilizing current values exceeding
End section 2
Equation 31