1MAC050144-MB C
Section 7
Control functions
615 series ANSI
483
Technical Manual
Figure 257:
Status indication based interlocking via GOOSE messaging
7.1.6
Signals
Table 414: 52 Input signals
Name
Type
Default
Description
ENA_OPEN
BOOLEAN
1=True
Enables opening
ENA_CLOSE
BOOLEAN
1=True
Enables closing
BLK_OPEN
BOOLEAN
0=False
Blocks opening
BLK_CLOSE
BOOLEAN
0=False
Blocks opening
ITL_BYPASS
BOOLEAN
0=False
Discards ENA_OPEN and ENA_CLOSE interlocking when TRUE
AU_OPEN
BOOLEAN
0=False
Input signal used to open the breaker
1
1. Not available for monitoring
AU_CLOSE
BOOLEAN
0=False
Input signal used to close the breaker
POSOPEN
BOOLEAN
0=False
Signal for open position of apparatus from I/O
POSCLOSE
BOOLEAN
0=False
Signal for closed position of apparatus from I/O