1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
209
Technical Manual
Table 196: 46M Non group settings
4.1.9.9
Monitored data
Table 197: 46M Monitored data
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Rated current
0.30...2.00
xIn
0.01
1.00
Rated current (Ir) of the machine (used only in the IDMT)
Maximum trip time
500000...7200000
ms
1000
1000000
Max trip time regardless of the inverse characteristic
Minimum trip time
100...120000
ms
1
100
Minimum trip time for IDMT curves
Cooling time
5...7200
s
1
50
Time required to cool the machine
Reset delay time
0...60000
ms
1
20
Reset delay time
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
T_ENARESTART
FLOAT32
0.00...7200.00
s
Estimated time to reset of block restart
46M
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......