1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
229
Technical Manual
Table 226: 59-1/2 Non group settings
4.2.1.9
Monitored data
Table 227: 59-1/2 Monitored data
Parameter
Values (Range)
Unit Step Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required for trip activation
Minimum trip time
40...60000
ms
1
40
Minimum trip time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Curve parameter A
0.005...200.000
1.000
Parameter A for customer programmable curve
Curve parameter B
0.50...100.00
1.00
Parameter B for customer programmable curve
Curve parameter C
0.0...1.0
0.0
Parameter C for customer programmable curve
Curve parameter D
0.000...60.000
0.000
Parameter D for customer programmable curve
Curve parameter E
0.000...3.000
1.000
Parameter E for customer programmable curve
Curve Sat Relative
0.0...3.0
0.1
2.0
Tuning parameter to avoid curve discontinuities
Voltage selection
1=phase-to-ground
2=phase-to-phase
2=phase-to-phase
Parameter to select phase or phase-to-phase voltages
Relative hysteresis
1.0...5.0
%
0.1
4.0
Relative hysteresis for operation
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
59-1/2
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......