Section 13
1MAC050144-MB C
Technical data
692
615 series ANSI
Technical Manual
Table 567: Energizing inputs
Table 568: Binary inputs
Description
Value
Rated frequency
50/60 Hz
Current inputs
Rated current, I
n
0.2/1 A
1)2)
1/5 A
3)
Thermal withstand capability:
• Continuously
• For 1 s
4 A
100 A
20 A
500 A
Dynamic current withstand:
• Half-wave value
250 A
1250 A
Input impedance
<100 mΩ
<20 mΩ
Voltage inputs
Rated voltage, V
n
60...210 V AC
Voltage withstand:
• Continuous
• For 10 s
2 x V
n
(240 V AC)
3 x V
n
(360 V AC)
Burden at rated voltage
<0.05 VA
1) Ordering option for ground current input
2) Not available for RET615
3) Ground current and/or phase current
Description
Value
Operating range
±20% of the rated voltage
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
18...176 V DC
Reaction time
3 ms