Section 7
1MAC050144-MB C
Control functions
522
615 series ANSI
Technical Manual
In the command control mode operation, there are alarms for a failed closing attempt
(CL_FAIL_AL) and for a command signal that remains active too long
(CMD_FAIL_AL).
If the conditions for closing are not fulfilled within set time of Maximum Syn time, a failed
closing attempt alarm is given. The CL_FAIL_AL alarm output signal is pulse shaped and
the pulse length is 500 ms. If the external command signal is removed too early, that is,
before conditions are fulfilled and close pulse is given, the alarm timer is reset.
.
Figure 286:
Determination of the checking time for closing
The control module receives information about the circuit breaker status and thus is able
to adjust the command signal to be delivered to the synchrocheck function. If the external
command signal CL_COMMAND is kept active longer than necessary, CMD_FAIL_AL
alarm output is activated. The alarm indicates that the control module has not removed
the external command signal after the closing operation. To avoid unnecessary alarms, the
duration of the command signal should be set in such a way that the maximum length of
the signal is always below Maximum Syn time + 5s.
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......