Section 6
1MAC050144-MB C
Supervision functions
438
615 series ANSI
Technical Manual
Figure 231:
Incorrect testing of IEDs
6.2.6
Signals
Table 378: TCM Input signals
Table 379: TCM Output signals
6.2.7
Settings
Table 380: TCM Non group settings
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block input status
Name
Type
Description
ALARM
BOOLEAN
Alarm output
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
1=Enable
Operation Disable / Enable
Trip delay time
20...300000
ms
1
3000
Operate delay time
Reset delay time
20...60000
ms
1
1000
Reset delay time