Section 4
1MAC050144-MB C
Protection functions
354
615 series ANSI
Technical Manual
Figure 171:
Differential protection of a three-winding transformer and a transformer
with two output feeders
Transforming ratio correction of CTs
First, the rated load of the power transformer must be calculated on both sides when the
apparent power and phase-to-phase voltage are known.
(Equation 42)
I
nT
rated load of the power transformer
S
n
rated power of the power transformer
V
n
rated phase-to-phase voltage
Next, the settings for the CT ratio correction can be calculated.
(Equation43)
After the CT ratio correction, the measured currents and corresponding setting values of
87T are expressed in multiples of the rated power transformer current Ir (xIn) or
percentage value of Ir (%Ir).