Section 3
1MAC050144-MB C
Basic functions
100
615 series ANSI
Technical Manual
3.13.2.3
Minimum minute pulse timer 62CLD-2
Identification
Function block
Figure 40:
Function block
Functionality
The Minimum minute pulse timer function 62CLD-2 contains two independent timers.
The function has a settable pulse length (in minutes). The timers are used for setting the
minimum pulse length for example, the signal outputs. Once the input is activated the
function gives out a pulse (Cold load time setting). But if the input remains active longer
than the set Cold load time, also the output remains active until the input is deactivated
Functional description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Minimum minute pulse timer
TPMGAPC
TPM (1)
62CLD-2
62CLD2
IN2
IN1
OUT1
OUT2