Section 3
1MAC050144-MB C
Basic functions
40
615 series ANSI
Technical Manual
Table 6:
Analog input settings, phase voltages
Table 7:
Analog input settings, residual voltage
Table 8:
Programmable LED Input signals
Parameter
Values (Range)
Unit
Step
Default
Description
Primary voltage
0.001...440.000
kV
0.001
20.000
Primary rated voltage
Secondary voltage
60...210
V
1
100
Secondary rated voltage
VT connection
1=Wye
2=Delta
3=U12
4=UL1
2=Delta
Wye, delta, U12 orUL1 VT connection
Amplitude corr. A
0.900...1.100
0.001
1.000
Phase A Voltage phasor magnitude correction of an external
voltage transformer
Amplitude corr. B
0.900...1.100
0.001
1.000
Phase B Voltage phasor magnitude correction of an external
voltage transformer
Amplitude corr. C
0.900...1.100
0.001
1.000
Phase C Voltage phasor magnitude correction of an external
voltage transformer
Division ratio
1000...20000
1
10000
Voltage sensor division ratio
Table continues on next page
Voltage input type
1=Voltage trafo
3=CVD sensor
1=Voltage trafo
Type of the voltage input
Parameter
Values (Range)
Unit
Step
Default
Description
Secondary voltage
60...210
V
1
100
Secondary voltage
Primary voltage
0.001...440.000
kV
0.001
11.547
Primary voltage
Amplitude corr.
0.900...1.100
0.001
1.000
Amplitude correction
Name
Type
Default
Description
Programmable LED 1
BOOLEAN
0=False
Status of programmable LED 1
Programmable LED 2
BOOLEAN
0=False
Status of programmable LED 2
Programmable LED 3
BOOLEAN
0=False
Status of programmable LED 3
Programmable LED 4
BOOLEAN
0=False
Status of programmable LED 4
Programmable LED 5
BOOLEAN
0=False
Status of programmable LED 5
Programmable LED 6
BOOLEAN
0=False
Status of programmable LED 6
Programmable LED 7
BOOLEAN
0=False
Status of programmable LED 7
Programmable LED 8
BOOLEAN
0=False
Status of programmable LED 8
ProgrammableALED 9
BOOLEAN
0=False
Status of programmable LED 9
Programmable LED 10
BOOLEAN
0=False
Status of programmableLED 10
Programmable LED 11
BOOLEAN
0=False
Status of programmableLED 11
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......