1MAC050144-MB C
Section 3
Basic functions
615 series ANSI
107
Technical Manual
GUID-43078009-323D-409C-B84A-5EB914CDEE53 V1 EN
Figure 43:
Load profile record file naming
3.15.1.4
Clearing of record
The load profile record can be cleared with
Reset load profile rec
via HMI, communication
or the ACT input in PCM600. Clearing of the record is allowed only on the engineer and
administrator authorization levels.
The load profile record is automatically cleared if the quantity selection parameters are
changed or any other parameter which affects the content of the COMTRADE
configuration file is changed. Also, if data source for selected quantity is removed, for
example, with ACT, the load profile recorder stops recording and previously collected data
are cleared.
3.15.2
Configuration
The load profile record can be configured with the PCM600 tool or any tool supporting the
IEC 61850 standard.
The load profile record can be enabled or disabled with the
Operation
setting under the
Configuration/Load Profile Record
menu.
The mapping is done with the
Quantity selection
setting of the corresponding quantity
channel.
The recording buffer is filled in FIFO manner, meaning that oldest data is overwritten by
newest data. If oldest data is considered important,
Mem. warning level
and
Mem. alarm
level
parameters can be set to get notification about memory consumtion reaching certain
level. Therefore the data can be uploaded before oldest data gets overwritten. To re-enable
notifications via
Mem. warning level
and
Mem. alarm level
parameters, the load profile
record should be cleared after uploading. State change of
Mem. warning level
or
Mem.
alarm level
parameters generates an event.
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......