Section 7
1MAC050144-MB C
Control functions
494
615 series ANSI
Technical Manual
Figure 266:
Logic diagram of auto-initiation sequence detection
Automatic initiation can be selected with the
Auto initiation Cnd
setting to be the
following:
• Not allowed: no automatic initiation is allowed
• When the synchronization fails, the automatic initiation is carried out when the auto
wait time elapses and the reclosing is prevented due to a failure during the
synchronism check
• When the circuit breaker does not close, the automatic initiation is carried out if the
circuit breaker does not close within the wait close time after issuing the reclose
command
• Both: the automatic initiation is allowed when synchronization fails or the circuit
breaker does not close.