1MAC050144-MB C
Section 5
Protection related functions
615 series ANSI
407
Technical Manual
protecting the outgoing feeders, which in turn results in tripping of all circuit breakers of
the outgoing feeders. For maximum safety, the IEDs can be configured to trip all the circuit
breakers regardless of where the arc is detected.
Figure 206:
Arc flash detector with several IEDs
Arc flash detector with several IEDs and a separate arc flash detector
system
When realizing an arc flash detector with both IEDs and a separate arc flash detector
system, the cable terminations of the outgoing feeders are protected by IEDs using one lens
sensor for each IED. The busbar and the incoming feeder are protected by the sensor loop
of the separate arc flash detector system. With arc detection at the cable terminations, an
IED trips the circuit breaker of the outgoing feeder. However, when detecting an arc on
the busbar, the separate arc flash detector system trips the circuit breaker of the incoming
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......