1MAC050144-MB C
Section 7
Control functions
615 series ANSI
491
Technical Manual
Figure 263:
Signal scheme of autoreclose operation initiated with protection pickup
signal
The autoreclose shot is initiated with a trip signal of the protection function after the
pickup delay time has elapsed. The autoreclose picks up when the
Str 2 delay shot 1
setting
elapses.
Figure 264:
Signal scheme of autoreclose operation initiated with protection trip
signal
The autoreclose shot is initiated with a trip signal of the protection function. The
autoreclose picks up when the protection trip delay time elapses.
Normally, all trip and pickup signals are used to initiate an autoreclose shot and trip the
circuit breaker. If any of the input signals
INIT_X
or
DEL_INIT_X
are used for
blocking, the corresponding bit in the
Tripping line
setting must be FALSE. This is to
ensure that the circuit breaker does not trip from that signal, that is, the signal does not
activate the
OPEN_CB
output. The default value for the setting is "63", which means that
all initiation signals activate the
OPEN_CB
output. The lowest bit in the
Tripping line
setting corresponds to the
INIT_1
input, the highest bit to the
INIT_6
line.
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......