Section 4
1MAC050144-MB C
Protection functions
190
615 series ANSI
Technical Manual
Table 173: 67/50N-2 Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
0.10...40.00
xIn
0.01
0.10
Pickup value
Pickup value mult
0.8...10.0
0.1
1.0
Multiplier for scaling the pickup value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Time multiplier
0.05...15.00
0.05
1.00
Time multiplier in IEC/ANSI IDMT curves
Operating curve type
1=ANSI Ext Inv
3=ANSI Norm Inv
5=ANSI DT
15=IEC DT
17=Programmable
5=ANSI DT
Selection of time delay curve type
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Trip delay time
40...200000
ms
10
40
Trip delay time
Operation mode
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle
Operation criteria
Characteristic angle
-179...180
deg
1
-90
Characteristic angle
Max forward angle
0...180
deg
1
88
Maximum phase angle in forward direction
Max reverse angle
0...180
deg
1
88
Maximum phase angle in reverse direction
Min forward angle
0...180
deg
1
88
Minimum phase angle in forward direction
Min reverse angle
0...180
deg
1
88
Minimum phase angle in reverse direction
Voltage pickup value
0.010...1.000
xVn
0.001
0.010
Voltage pickup value
Enable voltage limit
0=False
1=True
1=True
Enable voltage limit
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......