1MAC050144-MB C
Section 7
Control functions
615 series ANSI
513
Technical Manual
Fourth delay in SOTF
0=False
1=True
0=False
Sets 4th delay into use for all DEL_INIT signals
during SOTF
First reclose time
0...300000
ms
10
5000
Dead time for CBB1
Second reclose time
0...300000
ms
10
5000
Dead time for CBB2
Third reclose time
0...300000
ms
10
5000
Dead time for CBB3
Fourth reclose time
0...300000
ms
10
5000
Dead time for CBB4
Fifth reclose time
0...300000
ms
10
5000
Dead time for CBB5
Sixth reclose time
0...300000
ms
10
5000
Dead time for CBB6
Seventh reclose time
0...300000
ms
10
5000
Dead time for CBB7
Init signals CBB1
0...63
0
Initiation lines for CBB1
Init signals CBB2
0...63
0
Initiation lines for CBB2
Init signals CBB3
0...63
0
Initiation lines for CBB3
Init signals CBB4
0...63
0
Initiation lines for CBB4
Init signals CBB5
0...63
0
Initiation lines for CBB5
Init signals CBB6
0...63
0
Initiation lines for CBB6
Init signals CBB7
0...63
0
Initiation lines for CBB7
Blk signals CBB1
0...63
0
Blocking lines for CBB1
Blk signals CBB2
0...63
0
Blocking lines for CBB2
Blk signals CBB3
0...63
0
Blocking lines for CBB3
Blk signals CBB4
0...63
0
Blocking lines for CBB4
Blk signals CBB5
0...63
0
Blocking lines for CBB5
Blk signals CBB6
0...63
0
Blocking lines for CBB6
Blk signals CBB7
0...63
0
Blocking lines for CBB7
Shot number CBB1
0...5
0
Shot number for CBB1
Shot number CBB2
0...5
0
Shot number for CBB2
Shot number CBB3
0...5
0
Shot number for CBB3
Shot number CBB4
0...5
0
Shot number for CBB4
Shot number CBB5
0...5
0
Shot number for CBB5
Shot number CBB6
0...5
0
Shot number for CBB6
Shot number CBB7
0...5
0
Shot number for CBB7
Str 2 delay shot 1
0...300000
ms
10
0
Delay time for start2, 1st reclose
Str 2 delay shot 2
0...300000
ms
10
0
Delay time for start2 2nd reclose
Str 2 delay shot 3
0...300000
ms
10
0
Delay time for start2 3rd reclose
Str 2 delay shot 4
0...300000
ms
10
0
Delay time for start2, 4th reclose
Str 3 delay shot 1
0...300000
ms
10
0
Delay time for start3, 1st reclose
Str 3 delay shot 2
0...300000
ms
10
0
Delay time for start3 2nd reclose
Str 3 delay shot 3
0...300000
ms
10
0
Delay time for start3 3rd reclose
Str 3 delay shot 4
0...300000
ms
10
0
Delay time for start3, 4th reclose
Str 4 delay shot 1
0...300000
ms
10
0
Delay time for start4, 1st reclose
Str 4 delay shot 2
0...300000
ms
10
0
Delay time for start4 2nd reclose
Str 4 delay shot 3
0...300000
ms
10
0
Delay time for start4 3rd reclose
Parameter
Values (Range)
Unit
Step Default
Description
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......