Rev13 29-10-2019
Victron Energy B.V. / De Paal 35 / 1351 JG ALMERE / Nederland
Telefoon: (+31) (0)36 535 97 00 /
/ E-mail: [email protected]
BatteryProtect 12/24V
ENGLISH
Installation
1. The BatteryProtect (BP) must be installed in a well-ventilated area and preferably close (max 50 cm) to
the battery (but, due to possible corrosive gasses not above the battery!).
Voltage drop over a long or
undersized cable between the battery plus and the BP may result in a short circuit alarm when starting-
up the load, or unexpected shutdown.
2. A properly sized fuse must be inserted according to local regulations in the cable between the battery
and the BP.
3. The BP is designed to allow current to flow from IN (battery) to OUT
(load) terminals only.
Reverse currents from OUT to IN terminals are strictly forbidden, and
will damage the device. If you wish to use the BP as a disconnection
for a charge source, you must orient the unit in the system so that the
current is flowing in the intended direction, IN to OUT.
4. The short circuit protection of the BP will be activated if you try to
directly connect loads with capacitors on their input (eg inverters). For
that use case, please use the BP to control the remote on/off switch
on the inverter, instead of disconnecting the higher power DC line.
5. Use a 1,5mm² wire (included) for the minus connection, which should be connected directly to the
battery minus. No other equipment should be connected to this wire.
6. The BP automatically detects the system voltage
one time only
after connection of plus and minus to the
battery. The selected voltage (12 or 24V) is stored, and further automatic detection is disabled. See
in the
programming table for how to reset it when re-using the BP in a different installation.
7. Do not connect the load output until the BP has been fully programmed.
8. A remote on-off switch can be connected to the two pole connector (see figure 1) or between pin 2-1 of
the two pole connector and the battery plus.
9. A buzzer, LED or relay can be connected between the alarm output and the battery plus (see figure 1).
Maximum load on the alarm output: 50 mA (short circuit proof).
Load disconnect events and alarm output options
Buzzer or LED mode (buzzer or LED connected to the alarm output):
•
In case of under voltage, a continuous alarm will start after 12 seconds. The BP will disconnect the
load after 90 seconds and the alarm will stop. Reconnect delay: 30 seconds.
•
In case of over voltage, the load will be disconnected immediately and an intermittent alarm will
remain on until the overvoltage problem has been corrected. There is no reconnect delay.
Relay mode (relay connected to the alarm output):
•
In case of under voltage, the relay will engage after 12 seconds. The BP will disconnect the load after
90 seconds and the relay will disengage.
•
In case of over voltage, the load will be disconnected immediately and the alarm output will remain
inactive. Overvoltage trip levels: 16V respectively 32V
Li-ion mode:
•
Connect the load disconnect output of the VE.Bus BMS to pin 2-1.
The load is disconnected immediately when the load disconnect output of the VE.Bus BMS switches
from ‘high’ to ‘free floating’ (due to battery cell under voltage, over voltage or over temperature).
The under-voltage thresholds and alarm output of the BP are inactive in this mode.
Operation
There are 4 possible error modes, indicated by the 7-segment display:
•
Short circuit detected
•
Over load or over temperature
•
Under voltage
•
Over voltage
After 5 minutes the error is no longer displayed to reduce current consumption.
The decimal point of the 7-segment display is used for status indication:
•
On solid: the BP attempts to activate the output
•
Flash every 5s: output is active
•
Flashing every 2s in Li-ion mode: output ‘connecting’
Remote control and short circuit
•
The BP will connect the load 1 second after closing the remote contact.
•
The BP will disconnect the load immediately when the remote contact is opened.
•
When in Li-ion mode the BP will connect the load 30 seconds after the remote input of the BP has
been pulled high by the VE.Bus BMS. This delay increases to 3 minutes in case of frequent switching.
•
In case of a short circuit, the BP will attempt to connect the load every 5 seconds. After two attempts
the display will show
(short circuit detected).
Programming
When switched off (remote open), the BP can be programmed for the desired voltages and modes by
connecting the PROG pin to ground. Please see the programming table.
The display will first step through the shutdown and restart voltages. Disconnect the PROG pin when the
desired voltage is displayed.
The display will confirm the chosen voltage and default mode (
) twice.
Reconnect the PROG pin to ground if another mode is (
,
or
is required. Disconnect when the required
mode is displayed.
The display will confirm the chosen voltage and mode twice.
Programming table
7 segment display
Under voltage shut down
12V / 24V system
Under voltage restart
12V / 24V system
10,5V / 21V
12V / 24V
10V / 20V
11,5V / 23V
9,5V / 19V
11,5V / 23V
11,25V / 22,5V
13,25V / 26,5V
11,5V / 23V
13,8V / 27,6V
10,5V / 21V
12,8V / 25,6V
11,5V / 23V
12,8V / 25,6V
11,8V / 23,6V
12,8V / 25,6V
12V / 24V
13V / 26V
10V / 20V
13,2V / 26,4V
Buzzer or LED mode
Relay mode
Li-ion mode
Detect system voltage
Specifications
BatteryProtect
BP-65
BP-100
BP-220
Maximum cont. load current
65A
100A
220A
Peak current
250A
600A
600A
Operating voltage range
6 –35V
Current consumption
When on: 1,5 mA When off or low voltage shutdown: 0,6 mA
Alarm output delay
12 seconds
Max. load on alarm output
50mA (short circuit proof)
Load disconnect delay
90 seconds
(immediate if triggered by the VE.Bus BMS)
Load reconnect delay
30 seconds
Default thresholds
Disengage: 10,5V or 21V Engage: 12V or 24V
Operating temperature range
Full load: -40°C to +40°C
(up to 60% of nominal load at 50°C)
Connection
M6
M8
M8
Weight
0,2kg 0.5 lbs
0,5kg 0.6 lbs
0,8kg 1.8 lbs
Dimensions (hxwxd)
40 x 48 x 106 mm
1.6 x 1.9 x 4.2 inch
59 x 42 x 115 mm
2.4 x 1.7 x 4.6 inch
62 x 123 x 120 mm
2.5 x 4.9 x 4.8 inch
Example Wiring Diagrams
OUT
OUT
IN
IN
OUT
IN
IN
OUT