Section 7
1MAC050144-MB C
Control functions
488
615 series ANSI
Technical Manual
Figure 260:
Functional module diagram
7.2.4.1
Signal collection and delay logic
When the protection trips, the initiation of autoreclose shots is in most applications
executed with the
INIT_1...6
inputs. The
DEL_INIT2...4
inputs are not used. In
some situations, pickup of the protection stage is also used for the shot initiation. This is
the only time when the
DEL_INIT
inputs are used.