Table 174: 67/50N-2 Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Reset delay time
0...60000
ms
1
20
Reset delay time
Minimum trip time
40...60000
ms
1
40
Minimum trip time for IDMT curves
Allow Non Dir
0=False
1=True
0=False
Allows prot activation as non-dir when dir info is invalid
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Min trip current
0.005...1.000
xIn
0.001
0.005
Minimum trip current
Min trip voltage
0.01...1.00
xVn
0.01
0.01
Minimum trip voltage
Correction angle
0.0...10.0
deg
0.1
0.0
Angle correction
Pol reversal
0=False
1=True
0=False
Rotate polarizing quantity
Curve parameter A
0.0086...120.0000
28.2000
Parameter A for customer programmable curve
Curve parameter B
0.0000...0.7120
0.1217
Parameter B for customer programmable curve
Curve parameter C
0.02...2.00
2.00
Parameter C for customer programmable curve
Curve parameter D
0.46...30.00
29.10
Parameter D for customer programmable curve
Curve parameter E
0.0...1.0
1.0
Parameter E for customer programmable curve
Io signal Sel
1=IG
2=I0
1=IG
Selection for used Io signal
Pol signal Sel
1=Measured VG
2=Calculated V0
3=Neg. seq. volt.
2=Calculated V0
Selection for used polarization signal
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......