Section 4
1MAC050144-MB C
Protection functions
146
615 series ANSI
Technical Manual
Figure 67:
Closed ring network topology where feeding lines are protected with
directional overcurrent IEDs
4.1.3.8
Signals
Table 124: 67/51P-1 and 67/50P-1 Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
I
2
SIGNAL
0
Negative phase sequence current
V_A_AB
SIGNAL
0
Phase to ground voltage A or phase to phase voltage AB
V_B_BC
SIGNAL
0
Phase to ground voltage B or phase to phase voltage BC
V_C_CA
SIGNAL
0
Phase to ground voltage C or phase to phase voltage CA
V
1
SIGNAL
0
Positive phase sequence voltage
V
2
SIGNAL
0
Negative phase sequence voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
ENA_MULT
BOOLEAN
0=False
Enable signal for current multiplier