1MAC050144-MB C
Section 3
Basic functions
615 series ANSI
103
Technical Manual
3.13.3.5
Monitored data
Table 82:
CONTROL Monitored data
3.14
Factory settings restoration
In case of configuration data loss or any other file system error that prevents the IED from
working properly, the whole file system can be restored to the original factory state. All
default settings and configuration files stored in the factory are restored. For further
information on restoring factory settings, see the operation manual.
3.15
Load profile record LDPMSTA
3.15.1
Functionality
The IED is provided with a load profile recorder. The load profile feature stores the
historical load data captured at a periodical time interval (demand interval). Up to 12 load
quantities can be selected for recording and storing in a nonvolatile memory. The value
range for the recorded load quantities is about eight times the nominal value, and values
larger than that saturate. The recording time depends on a settable demand interval
Parameter
Type
Values (Range)
Unit
Description
Command
response
ENUM
1 = "Select open"
2 = "Select close"
3 = "Operate open"
4 = "Operate close"
5 = "Direct open"
6 = "Direct close"
7 = "Cancel"
8 = "Position reached"
9 = "Position timeout"
10 = "Object status only"
11 = "Object direct"
12 = "Object select"
13 = "RL local allowed"
14 = "RL remote allowed"
15 = "RL off"
16 = "Function off"
17 = "Function blocked"
18 = "Command progress"
19 = "Select timeout"
20 = "Missing authority"
21 = "Close not enabled"
22 = "Open not enabled"
23 = "Internal fault"
24 = "Already close"
25 = "Wrong client"
26 = "RL station allowed"
27 = "RL change"
Latest command response
LR state
ENUM
1 = "OFF"
2 = "Local"
3 = "Remote"
4 = "Station"
LR state monitoring for
PCM
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......