Section 4
1MAC050144-MB C
Protection functions
120
615 series ANSI
Technical Manual
Table 95:
50P-1/2 Output signals
Table 96:
50P-3 Output signals
4.1.1.9
Settings
Table 97:
51P Group settings
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
0.05...5.00
xIn
0.01
1.00
Pickup value
Pickup value mult
0.8...10.0
0.1
1.0
Multiplier for scaling the pickup value
Time multiplier
0.05...15.00
0.05
1.00
Time multiplier in IEC/ANSI IDMT curves
Trip delay time
40...200000
ms
10
40
Trip delay time
Operating curve type
1=ANSI Ext Inv
2=ANSI Very Inv
3=ANSI Norm Inv
4=ANSI Mod Inv
5=ANSI DT
6=LT Ext Inv
7=LT Very Inv
8=LT Inv
9=IEC Norm Inv
10=IEC Very Inv
11=IEC Inv
12=IEC Ext Inv
13=IEC ST Inv
14=IEC LT Inv
15=IEC DT
17=Programmable
18=RI Type
19=RD Type
5=ANSI DT
Selection of time delay curve type
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......