background image

3-Phase 

Power Distribution Unit

USER'S MANUAL

Copyright © 2019 Cyber Power Systems, Inc. All rights reserved.                       K01-0000699-00

Summary of Contents for PDU13101

Page 1: ...3 Phase Power Distribution Unit USER S MANUAL Copyright 2019 Cyber Power Systems Inc All rights reserved K01 0000699 00...

Page 2: ...18 PDU Installation 18 Power Cord Direction Change For Selected PDU Models 22 Locking Power Cord For IEC Type PDU 23 Output Power Cord 23 Electrical Installation 23 Network Installation 24 Operation 2...

Page 3: ...U43402 PDU43104 PDU43108 PDU43403 Monitored Series PDU33101 PDU33106 PDU331 1 1 PDU33102 PDU33107 PDU33112 PDU33103 PDU33108 PDU33121 PDU33104 PDU33109 PDU33401 PDU33105 PDU33110 PDU33402 Basic Series...

Page 4: ...please use a 50A circuit protector For 60A PDU series please use a 60A circuit protector Connection to any other type of power outlet may result in a shock hazard Do not use extension cords or adapte...

Page 5: ...30 to 36 outlet PDU Qty 70 42 to 48 outlet PDU RJ45 DB9 Serial Port Connection Cable User s Manual Registration Card and Software Download Card Users Manual Registration Card PowerPanel Management Sof...

Page 6: ...In ENV USB Serial Out Link 6 7 8 1 2 3 4 5 9 10 16 17 18 11 12 13 14 15 19 20 26 27 28 21 22 23 24 25 29 30 L1 L2 L3 L1 L2 L3 A B B B D E F G H C I K L J C C PDU83102 L21 20P Critical Warning Normal E...

Page 7: ...o C Safety Approvals Certifications UL60950 1 UL62368 1 FCC Class A CB CE EN55032 24 Class A All specifications are subject to change without notice A AC Inlet AC Power Cord Used to connect PDU to uti...

Page 8: ...Panel N N N L21 30P Critical Warning Normal Enter Select Tx Rx In ENV USB Serial Out Link BANK 3 20A BANK 2 20A BANK 1 20A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29...

Page 9: ...ithout notice A AC Inlet AC Power Cord Used to connect PDU to utility power or UPS B Circuit Breaker Provides overload protection C Outlet Indicator switched series only Indicates if the outlet is pro...

Page 10: ...5o C to 55o C Safety Approvals Certifications CB CE EN55032 24 Class A All specifications are subject to change without notice Technical Specifications Model Name PDU83107 PDU43107 PDU83108 PDU43108...

Page 11: ...101 Critical Warning Normal Enter Select Tx Rx In ENV USB Serial Out Link 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 A B C D E F G B B H J K I P...

Page 12: ...ure 23o F to 140o F 5o C to 60o C 23o F to 131o F 5o C to 55o C Safety Approvals Certifications UL 60950 1 UL62368 1 FCC Class A UL 60950 1 UL62368 1 FCC Class A CB CE EN55032 24 Class A All specifica...

Page 13: ...32 50 60A Models Front Rear Panel Description IEC Type Rear Panel M M M IEC 309 30A 3P E PDU33107 Critical Warning Normal Enter Select Tx Rx In ENV USB Serial Out Link BANK 1 20A BANK 2 20A BANK 3 20A...

Page 14: ...0 to 95 Non condensing Altitude 11480 ft 3500 m Temperature 23o F to 140o F 5o C to 60o C 23o F to 131o F 5o C to 55o C 23o F to 140o F 5o C to 60o C Safety Approvals Certifications UL60950 1 UL62368...

Page 15: ...35A UL Derated Outlet Type 6 IEC 320 C13 12 IEC 320 C19 30 IEC 320 C13 6 IEC 320 C19 30 IEC 320 C13 42 IEC 320 C13 6 IEC 320 C19 Outlet Number 18 36 30 48 Management and Communications Multifunction...

Page 16: ...n NEMA Type IEC Type Rear Panel A AC Inlet AC Power Cord Used to connect PDU to utility power or UPS B AC Output Receptacles Provides power for connected equipment C Bracket Screw Hole Used to secure...

Page 17: ...tput Current 16A UL Derated 16A CE Outlet Type 42 NEMA 5 20R 36 IEC 320 C13 6 IEC 320 C19 21 NEMA 5 20R 6 NEMA L6 20R 36 IEC 320 C13 6 IEC 320 C19 Outlet Number 42 42 27 42 Physical Dimensions H x W x...

Page 18: ...Cord Used to connect PDU to utility power or UPS B Circuit Breaker Provides overload protection C AC Output Receptacles Provides power for connected equipment D Bracket Screw Hole Used to secure the M...

Page 19: ...ngth 10 ft 3 05 m Output Nominal Voltage 200 240V Maximum Output Current 35A UL Derated 32A CE Outlet Type 30 IEC 320 C13 6 IEC 320 C19 36 IEC 320 C13 6 IEC 320 C19 Outlet Number 36 42 Physical Dimens...

Page 20: ...re is no Keyhole Slot on your rack please choose from the following methods that is best for your rack deployment to secure the PDU Use the supplied Washers and Rack Mounting Screws to attach the Moun...

Page 21: ...19 Installation Guide Method 2...

Page 22: ...20 Method 3 Installation Guide...

Page 23: ...tion Tray to the PDU with the supplied Cord Retention Tray Mounting Screws Tighten the Cord Retention Tray with the screw on it Use the provided Cable Ties to fasten each cord to the Cord Retention Tr...

Page 24: ...irection Change For Selected PDU Models Step 1 Remove the four screws from the power cord cover Keep the screws for later use Step 2 Rotate the power cord cover Step 3 Install the power cord cover bac...

Page 25: ...wer source Step 3 Attach equipment It is extremely important not to exceed the PDUs maximum current load as outlined in the Specifications section In order to determine your total load simply use the...

Page 26: ...word is cyber Option 2 DHCP Server 1 Ask your administrator if there is DHCP server on the LAN 2 Make sure the DHCP is Enabled 3 Make sure the network connection is ready and power on the PDU 4 The PD...

Page 27: ...for SNMPv1 SNMPv3 provides a higher security level than SNMPv1 by encrypting the transmitted packet Configure the settings of the SNMPv1 SNMPv3 on Web Interface Local Management LCD Operation The LCD...

Page 28: ...own on the connected computer s operating system PowerPanel must be installed on every computer or server for which the shutdown is to take place The computer will receive a message from the PDU and w...

Page 29: ...e 1 The FTP service needs to be enabled before attempting to execute a firmware upgrade 2 Please do not turn the PDU off when performing the firmware upgrade PDU outlets will remain powered on while t...

Page 30: ...following steps to upgrade the firmware 1 Download the Upgrade and Configuration Utility from www cyberpower com 2 Open Upgrade and Configuration Utility from Start All Programs CyberPower Upgrade and...

Page 31: ...updated Shown in Figure 4 Firmware Upgrade Figure 4 8 Click OK in the Upgrade Firmware confirmation window Shown in Figure 5 9 The upgrade progress bar will show in Last Action column Shown in Figure...

Page 32: ...ain USB USB Firmware Firmware Firmware Firmware Upgrade Upgrade Upgrade Upgrade Main Confirm Processing Success Return Yes No Main Menu Alert Meter Control Sensor Setting About USB 4 Select USB and pr...

Page 33: ...ission limits and also to prevent interference to the nearby radio and television reception It is essential that only the supplied power cord by used 2 Use only shielded cables to connect I O devices...

Page 34: ...roduct If the Product is defective in material or workmanship CyberPower will repair or replace it at CyberPower s expense or if CyberPower is unable to or decides not to repair or replace the Product...

Page 35: ...Configuration 4 Account Settings 5 Configure System to Default 6 Logout Outlet Manager 1 Outlet Control 2 Outlet Configuration Network Setting Physical MAC Address 00 0C 15 40 08 A9 1 System IP 192 16...

Page 36: ...Step 3 Choose an installation directory Select Next Shown in Figure 2 Figure 2 Step 4 Select Install to confirm the settings and install Shown in Figure 3 Figure 3 Step 5 Select Finish to finalize th...

Page 37: ...is allows the device s to function properly on the network and interface with CyberPower Management Console Step 1 Select the appropriate PDU device from the Equipment List Shown in Figure 6 Figure 6...

Page 38: ...ice at the Authentication menu Shown in Figure 9 Note The default username is cyber and the default password is cyber Advanced Settings Timeout Settings The Timeout Setting Shown in Figure 10 Edit Tim...

Page 39: ...Host PDU and the other end to the daisy chain In ENV port on the Guest 1 PDU to connect the PDUs as shown below How to connect the PDUs together Use one Ethernet cable and connect one end of it to th...

Page 40: ...w daisy chain where Guest 2 becomes a Host and Guest 3 becomes Guest 1 to the new Host In the above example if the disconnected Ethernet cable is re connected wil the role of the PDUs stay the same Ye...

Page 41: ...chained Yes even when the PDUs are daisy chained the Guest PDUs are able to connect to the network directly Note that a Guest PDU will require having its own Ethernet cable connected to the network Wh...

Page 42: ...Cyber Power Systems Inc www cyberpower com Copyright 2019 Cyber Power Systems Inc All rights reserved K01 0000699 00...

Reviews: