5
Product Features:
Switched Metered by Outlet/Switched
(16/20A Models)
Technical Specifications
Model Name
PDU83101
PDU43101
PDU83102
PDU43102
PDU83103
PDU43103
PDU83111
PDU43111
PDU83401
PDU43401
Input
Nominal Voltage
208V
200-240V
346-415V
Frequency
50/60Hz
Maximum Input Current
16A UL (Derated)
16A CE
Plug Type
NEMA L21-20P
NEMA
L15-20P
IEC 309
20A Red
(3P+N+E)
IEC 309
16A Red
(3P+N+E)
Power Cord Type
SR (12 AWG)
Power Cord Length
10 ft / 3.05 m
Output
Nominal Voltage
120V
200-240V
Maximum Output Current
16A UL (Derated)
16A CE
Outlet Type
(30) NEMA
5-20R
(24) IEC 320 C13 (6) IEC 320 C19
Outlet Number
30
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software
PowerPanel® Business Edition
Networking
Yes
Serial Port
RJ45
Sensor Capable
Optional
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
11480ft / 3500m
Temperature
23
o
F to 140
o
F / -5
o
C to 60
o
C
23
o
F to 131
o
F /
-5
o
C to 55
o
C
Safety Approvals
Certifications
UL60950-1, UL62368-1. FCC Class A
.
CB, CE
EN55032/24
Class A
* All specifications are subject to change without notice
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility
power or UPS.
B. Outlet Indicator (Switched Series only) - Indicates if the
outlet is providing power to connected equipment.
C. AC Output Receptacles - Provides power for connected
equipment.
D. Status Indicator - Indicates the condition of the PDU (eg.
load or environment status)
E. Multifunction LCD Readout - Displays various PDU
information such as power and load condition.
F. Ethernet Port – Used to connect PDU to the network.
G. ENVIROSENSOR/ Daisy Chain (In) Port (RJ45 modular port)
– Used for ENVIROSENSOR or chaining to previous PDU.
H. USB Port - Used to upgrade the firmware via a flash drive.
I. Serial Port (RJ45 modular port) - Used to connect to a PC
and control the PDU locally via SSH/Telnet.
J. Daisy Chain (Out) Port – Used for chaining to next PDU..
K. Select Button - Used to control the LCD screen and toggle
through the available information options
L. Enter Button - Used to choose selected items, enter to next
level menu or return to previous menu.
M. Bracket Screw Hole - Used to secure the Mounting Pegs (pre-
installed) or Mounting Brackets.