27
Operation
Step 3. Notification
Notifying the computers of potential outlet shutdown can be
accomplished using the following functions:
•
Outlets Control Menu: Performing the task of turning off or
rebooting outlets.
•
Scheduling Menu: Setting the PDU to perform the task of
turning off or rebooting outlets. The notification will occur
prior to the scheduled date/time.
•
Outlet Overload: In the event of PDU overload, notification will
be sent prior to the PDU shutting down.
Firmware Upgrade
By upgrading the Firmware, you can obtain new features and updates/
improvements to existing functionality. To ensure the firmware is
kept up to date, please regularly visit our website to see if there is
any updated firmware version available. There are three methods for
upgrading the PDU firmware. Please follow the instructions below for
the method that is appropriate for your application. There are two
files to update in order to upgrade the firmware version:
* cpsmpdumbfw_XXX.bin
* cpsmpdumbdata_XXX.bin
Note that the XXX is not part of the file name but is where the
version number in the filename is given.
Prior to performing a firmware update, please:
• Download the latest firmware from www.cyberpower.com.
• Extract the downloaded firmware file to your local “C:\” drive.
Note:
1. The FTP service needs to be enabled before attempting to
execute a firmware upgrade.
2. Please do not turn the PDU off when performing the firmware
upgrade. PDU outlets will remain powered on while the firmware
update takes place. Only the PDU LCD screen will reboot.
3. The PDU LCD screen will reboot during the firmware update
process. This DOES NOT cause the PDU outlets to reboot.
Option 1: Single Device Upgrade
Use the following steps to upgrade the firmware.
1. Open a command prompt window and navigate to “C:\”.
2. Login to the PDU with FTP command, type
- C:\>ftp
- ftp> open 192.168.22.126 21 (for example: 192.168.22.126
is the current IP of the PDU and 21 is the default ftp
port for the PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
3. Upload the cpsmpdumbfw_XXX.bin, type
- ftp > bin
- ftp > put cpsmpdumbfw_XXX.bin
4. Upgrade complete, type
- ftp > quit
5. The system will reboot after you type "quit". This reboot will take
approx. 30 seconds.
6. Login to the PDU via FTP again, type
- C:\>ftp
- ftp> open 192.168.22.126 21 (for example: 192.168.22.126
is the current IP of the PDU and 21 is the default ftp
port for the PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
7. Upload cpsmpdumbdata_XXX.bin, type
- ftp > bin
- ftp > put cpsmpdumbdata_XXX.bin
Summary of Contents for PDU13101
Page 21: ...19 Installation Guide Method 2...
Page 22: ...20 Method 3 Installation Guide...