DESCRIPTION

UNIPOWER’s UNIFLEX

®

 distribution panels 

provide the ultimate flexibility in combining 

fuses, circuit breakers and/or an LVD in a dual 

(A/B) panel.  A GMT section provides 10 fuses 

and a circuit breaker section, 1-6 breakers.

A low-voltage disconnect section is 

configured at the factory for either battery 

or load disconnect and can have an optional 

bypass switch. A battery circuit breaker is 

standard.

Each A and B section has an LED alarm 

indicator and Form C relay contacts.

The A and B Sections are isolated and can be 

configured independently at the factory for 

12, 24 or 48 VDC, positive or negative ground.

The panels are only one mounting position 

(1.75 inches) high and come with brackets 

that permit mounting in either a 19- or 

23-inch relay rack. They can be mounted 

from the front of the rack with offsets every 

quarter-inch from front to back to align with 

existing rack mounted equipment.

FEATURES

 

One Mounting Position High: 1.75”

 

19- or 23-Inch Rack Mounting

 

Dual Section (A/B)

 

Current Capacity per Section: 60A to 150A

 

Operating Voltage: 12, 24 or 48VDC

 

Positive or Negative Ground

 

A & B are Isolated Loads

 

LED Alarm Indicators

 

Form C Relay Contacts, Each Side

 

Combination of GMT Fuses, Breakers, LVD

 

1A to 50A Circuit Breakers

 

LVD has Battery Circuit Breaker

 

LVD in Series with Battery or Load

 

Rack Offset Every ¼” from Front to Back

SAFETY  CERTIFICATIONS

UL1950

CSA22.2, No. 950-95

THREE YEAR WARRANTY

DPU1U SERIES

UNIFLEX

®  

COMBINATION PANELS

Breakers | Fuses | LVD

AVAILABLE CONFIGURATIONS

BASE

MODEL

SIDE

TOTAL 

AMPS

TYPE

DPU1U

A

80 

150

10 x GMT Fuses

1-6 x Breakers

B

80 

150

70

10 x GMT Fuses

1-6 x Breakers

1 x LVD

Note:

  Each side of the panel can be configured for only 

one of the available ‘types’ as shown.  To specify a 

complete model number see the configuration 

guide on the following page.

LVD2006/95/EC

ROHS2011/65/EU

E210994

Summary of Contents for UNIFLEX DRU1U Series

Page 1: ...y can be mounted from the front of the rack with offsets every quarter inch from front to back to align with existing rack mounted equipment FEATURES One Mounting Position High 1 75 19 or 23 Inch Rack...

Page 2: ...w voltage disconnect specified by L 2 A bypass switch must also be designated YES or NO 3 For a breaker panel each breaker must be specified with highest current in position 1 down to lowest current i...

Page 3: ...N PANELS Document Number DPU1U MAN Rev 4 UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web site www unipowerco com 2019 UNIPOWER LLC All Rights Reser...

Page 4: ...TRODUCTION 4 2 0 FEATURES 5 3 0 PRODUCT DESCRIPTION 5 4 0 SAFETY INDUSTRY STANDARDS 6 5 0 WARRANTY summary 6 6 0 DESCRIPTION OF OPERATION 7 7 0 SPECIFICATIONS 8 8 0 FRONT PANEL DESCRIPTION 9 9 0 BACK...

Page 5: ...MT Fuse Section Front Panel View 9 Figure 6 LVD Front Panel View 9 Figure 7 Center Section Front Panel View 9 Figure 8 Back Panel View with LVD 10 Figure 9 Back Panel View with Dual Distribution 11 Fi...

Page 6: ...ng rackmounted equipment DPU1U Series provides a combination of circuit breaker or fuse distribution on the A side with an LVD or distribution on the B side Figure 1 shown the three possible combinati...

Page 7: ...GMT Fuses or Magnetic Circuit Breakers LVD Protection 70A Magnetic Circuit Breaker with Bypass Option Independent and Isolated Loads Input Connections Crimp Type Lugs Output Connections Barrier Termi...

Page 8: ...operating these combination anels the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel 4 5 All connections to these co...

Page 9: ...S OPTION Figure 2 Distribution Block Diagram 6 2 LVD Circuits Figure 3 shows a simplified diagram of the LVD circuit The LVD is connected to a rectifier bus battery and distribution panel The contact...

Page 10: ...Alarm Indicator LED on Each Side LED Status Fuse Breaker Sections Green Normal Red Alarm Off No Power LVD Section Red LVD Contactor or Battery Breaker Open Off Normal Alarm Connections Fuse Breaker Tw...

Page 11: ...F O ON I 15 17 12 434 9 REAR VIEW FRONT VIEW Cas Figure 4 Distribution Section Front Panel View The front panel of the GMT fuse distribution section shown in Figure 5 below can each accommodate up to...

Page 12: ...Red 3 401 1500 0060 Blue 401 1500 0020 Brown 5 401 1500 0070 Green 1 401 1500 0030 Gray 10 401 1500 0080 Red White 11 3 401 1500 0040 White 12 401 1500 0090 Green Yellow 2 401 1500 0050 Orange DUMMY...

Page 13: ...o spring clamp terminal blocks for the Form C relay contact outputs Below these is a chassis ground terminal 9 2 Input Connections also Output Connections for LVD See Figure 10 The DC power inputs to...

Page 14: ...mum of two high current breakers is allowed 1 2 3 4 5 6 7 8 9 10 40 50A LOADS 10 32 1A to 30A LOADS 6 32 0 75 19 1 0 5 12 7 0 378 9 60 Figure 11 Output Barrier Strip Detail 9 5 Form C Relay Contact Ou...

Page 15: ...is either loss of input power one or more circuit breakers trip or the relay is de energized the normally open contacts close and the normally closed contacts open See table 6 RELAY STATE MEANINGS Rel...

Page 16: ...Mount it from the front of the rack using the correct offsets to align with existing rack mounted equipment The bracket offsets are every quarter inch from front to back 11 2 Power Connections Input c...

Page 17: ...asure the resistance between C and N O This which should read open Measure the resistance between C and N C This should read short Replace the blown fuse with a good one or reset the circuit breaker 1...

Page 18: ...d application 12 4 If the combination panel did not operate properly in the above tests go back and double check the connections and the polarity of the input source to make sure it is correct Please...