Parameters
Parameter list
1-58
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
For parallel circuit configurations, the parameter index is assigned to a power module.
Description:
The overload conditions of the load duty cycles are valid under the prerequisite that before and after the overload
condition, the drive converter is operated with its base load current - this is based on a load duty cycle of 300 s.
The following applies for chassis drive units:
The base load current for a slight overload is based on a duty cycle of 110% for 60 s or 150% for 10 s.
The base load current for a high overload is based on a duty cycle of 150% for 60 s or 160% for 10 s.
The following applies for booksize drive units:
Only the setting p0205 = 0 can be selected. In this case, for the base load current, there is a load duty cycle of
150% for 60 s or 176% for 30 s.
Values:
0:
Load duty cycle with high overload condition for vector drives
1:
Load duty cycle with slight overload condition for vector drives
6:
S1 duty cycle for servo drives (feed drive)
7:
S6 duty cycle for servo drives (spindle drive)
Note:
When the parameter is changed, all of the motor parameters and the control type are pre-assigned according to the
selected application. The parameter has not influence when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power module EEPROM.
Its value is not reset when factory values are restored (see p0010 = 30, p0970).
Description:
Displays the rated power module power for various load duty cycles.
Index:
[0] = Rating plate
[1] = Load duty cycle with high overload condition
[2] = Load duty cycle with slight overload condition
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
The value is displayed in [kW] or [hp].
Refer to: p0100, p0205
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
DC/AC device
AC/AC device
DC/AC device
-
01
RFI filter available
No
Yes
-
02
Active line module available
No
Yes
-
04
Basic line module available with thyristor
bridge
No
Yes
-
05
Basic line module available with diode
bridge
No
Yes
-
12
Safe brake control (SBC) supported
Yes
No
-
p0205
Power module application / PM application
VECTOR
Can be changed:
C2
Access level:
3
Data type:
Integer16
Data set:
-
Function diagram:
-
P-Group:
Drive converter
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 7
6
r0206[0...4]
Rated power module power / PM P_rated
VECTOR
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Drive converter
Units group:
POWER_P3
Unit selection:
p0100
Min Max
Factory
setting
- [kW]
- [kW]
- [kW]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...