![Siemens SINAMICS G Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180036.webp)
Parameters
Parameter list
1-36
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Displays the closed-loop control status word 1 (closed-loop control STW1) of the drive.
Description:
Displays the actual speed/velocity setpoint at the input of the speed/velocity controller or V/f characteristic (after the
interpolator).
Dependency:
Refer to: r0020
Note:
The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).
Description:
Displays the speed/velocity sensed by the motor encoder (unsmoothed).
r0056
CO/BO: Closed-loop control status word 1 / Control_ZSW1
VECTOR
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Data set:
-
Function diagram:
6489,
6492
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
Initialization completed
No
Yes
-
01
De-magnetizing completed
No
Yes
-
02
Pulse enable present
No
Yes
-
03
Soft starting present
No
Yes
-
04
Magnetizing completed
No
Yes
-
06
Acceleration voltage active
No
Yes
-
07
Frequency negative
No
Yes
-
08
Field weakening active
No
Yes
-
09
Voltage limit active
No
Yes
-
10
Slip limit active
No
Yes
6310
11
Frequency limit active
No
Yes
-
12
Current limiting controller voltage output
active
No
Yes
-
13
Current limiting controller, freq output active not active
active
-
14
Vdc_max controller active
No
Yes
6220,
6320
15
Vdc_min controller active
No
Yes
6220,
6320
r0060
CO: Speed setpoint before the setpoint filter / n_set before filt.
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
2701,
5020, 6030
P-Group:
Displays, signals
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
- [1/min]
- [1/min]
- [1/min]
r0061
CO: Speed actual value motor encoder / n_act mot. encoder
VECTOR
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
1580,
4710, 6010
P-Group:
Displays, signals
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
- [1/min]
- [1/min]
- [1/min]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...