List of faults and alarms
Faults and Alarms
3-521
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
A01100
CU: CompactFlash Card withdrawn
Reaction:
NONE
Acknowledge:
NONE
Cause:
The CompactFlash Card (non-volatile memory) was withdrawn in operation.
Notice:
It is not permissible that the CompactFlash Card is withdrawn or inserted under voltage.
Remedy:
- power-down the drive system.
- re-insert the CompactFlash Card that was withdrawn - this card must match the drive system.
- power-up the drive system again.
F01105 (A)
CU: Insufficient memory
Reaction:
OFF1
Acknowledge:
IMMEDIATELY (power on)
Cause:
Two many functions, data sets or drives configured on this control unit.
Fault value (r0949, decimal):
Only for internal Siemens troubleshooting.
Remedy:
- change the configuration on this control unit.
- use an additional control unit.
Reaction upon A:
NONE
Acknowledge
upon A:
NONE
F01107
CU: Save to CompactFlash Card unsuccessful
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A data save on the CompactFlash Card was not able to be successfully carried-out.
- CompactFlash Card is defective.
- CompactFlash Card does not have sufficient memory space.
Fault value (r0949, decimal):
-1: The file on the RAM was not able to be opened.
-2: The file on the RAM was not able to be read.
-3. A new directory was not able to be set-up on the CompactFlash Card.
-4: A new file was not able to be set-up on the CompactFlash Card.
-5: A new file was not able to be written onto the CompactFlash Card.
Remedy:
- try to save again.
- use another CompactFlash Card.
F01110
CU: More than one SINAMICS G on one control unit
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
More than one SINAMICS G power module type is being operated from the control unit.
Fault value (r0949, decimal):
Number of the second drive with a SINAMICS G power module type.
Remedy:
Only one SINAMICS G drive type is permitted.
F01111
CU: SINAMICS S and G together on one control unit
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
SINAMICS S and G drive units are being operated together on one control unit.
Fault value (r0949, decimal):
Number of the first drive object with a different power module type.
Remedy:
Only power modules of one particular drive type may be operated with one CU.
F01120 (A)
Terminal initialization has failed
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY (power on)
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...