Parameters
Parameter list
1-268
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2182, p2183, p2189, p2190
Refer to: A07926
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2185 > p2186
Refer to: p2182, p2186
Refer to: A07926
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2186 < p2185
Refer to: p2182, p2185
Refer to: A07926
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2187 > p2188
Refer to: p2183, p2188
Refer to: A07926
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2188 < p2187
Refer to: p2183, p2187
Refer to: A07926
p2185[0...n]
Load monitoring torque threshold 1, upper / M_thresh 1 upper
VECTOR (Extended
msg)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
8013
P-Group:
Messages
Units group:
TORQUE
Unit selection:
-
Min Max
Factory
setting
0.00 [Nm]
99999.00 [Nm]
99999.00 [Nm]
p2186[0...n]
Load monitoring torque threshold 1, lower / M_thresh 1 lower
VECTOR (Extended
msg)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
8013
P-Group:
Messages
Units group:
TORQUE
Unit selection:
-
Min Max
Factory
setting
0.00 [Nm]
99999.00 [Nm]
0.00 [Nm]
p2187[0...n]
Load monitoring torque threshold 2, upper / M_thresh 2 upper
VECTOR (Extended
msg)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
8013
P-Group:
Messages
Units group:
TORQUE
Unit selection:
-
Min Max
Factory
setting
0.00 [Nm]
99999.00 [Nm]
99999.00 [Nm]
p2188[0...n]
Load monitoring torque threshold 2, lower / M_thresh 2 lower
VECTOR (Extended
msg)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
8013
P-Group:
Messages
Units group:
TORQUE
Unit selection:
-
Min Max
Factory
setting
0.00 [Nm]
99999.00 [Nm]
0.00 [Nm]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...