Parameters
Parameter list
1-164
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the controller configuration of the DC link voltage (Vdc controller) in the closed-loop control mode.
Values:
0:
Inhib Vdc ctrl
1:
Enables Vdc_max controller
2:
Enables Vdc_min controller (kinetic buffering)
3:
Enables Vdc_min controller and Vdc_max controller
Recommenda-
tion:
If fault F07403 is output, then proceed as follows:
- increase the dynamic factor (p1247).
- if this fault is still output: Increase the switch-on level (p1245).
Dependency:
Refer to: p1245
Refer to: F07403
Notice:
An excessively high value in p1245 can possibly negatively influence the normal operation of the drive.
Note:
p1240 = 1, 3:
When the DC link voltage limit, specified for the motor module is reached, the following applies:
- the Vdc_max controller limits the regenerative energy in order that the DC link voltage is kept below the maximum
DC link voltage when braking.
- the ramp-down times are automatically increased.
p1240 = 2, 3:
When the switch-in threshold of the Vdc_min controller is reached (p1245), the following applies:
- the Vdc_min controller limits the energy taken from the DC link in order to keep the DC link voltage above the min-
imum DC link voltage when accelerating.
- the motor is braked in order to use its kinetic energy to buffer the DC link.
Description:
Displays the switch-in level for the Vdc_max controller.
If p1254 = 0 (automatic sensing of the switch-in level = off), then the following applies:
AC/AC drive units: r1242 = 1.15 * sqrt(2) * V_line supply = 1.15 * sqrt(2) * p0210 (supply voltage)
DC/AC drive units: r1242 = 1.15 * Vdc = 1.15 * p0210 (supply voltage)
If p1254 = 1 (automatic sensing of the switch-in level = on), then the following applies:
r1242 = Vdc_max - 50.0 V (Vdc_max: overvoltage threshold of the power module)
01
Command, open brake (continuous signal)
No
Yes
2711
03
Pulse enable, expanded brake control
No
Yes
2711
04
Brake does not open
No
Yes
2711
05
Brake does not close
No
Yes
2711
06
Brake threshold exceeded
No
Yes
2707
07
Brake threshold fallen below
No
Yes
2704
08
Brake monitoring time expired
No
Yes
2704
09
Pulse or speed controller inhibited
No
Yes
2707
10
Brake OR logic operation result
No
Yes
2707
11
Brake AND logic operation result
No
Yes
2707
p1240[0...n]
Vdc controller configuration / Vdc_ctrl config
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Data set:
DDS
Function diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 3
1
r1242
Vdc_min controller switch-in level / Vdc_max on_level
VECTOR (n/M)
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
6220
P-Group:
Functions
Units group:
VOLTAGE_DC
Unit selection:
-
Min Max
Factory
setting
- [V]
- [V]
- [V]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...