Parameter list
Parameters
1-181
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Displays closed-loop control status word 3 (closed-loop control STW3).
Description:
Sets the time constant for the speed/velocity setpoint filter 1 (PT1).
Note:
For SERVO (p0107) the following applies:
This parameter is only effective if the speed filter is set as a PT1 low pass.
Description:
Sets the deadtime to balance the speed/velocity setpoint for active torque/force pre-control.
The selected multiplier refers to the speed/velocity controller clock cycle (deadtime= p1428 * p0115[1]).
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
V/f control active
No
Yes
-
01
Sensorless operation active
No
Yes
-
02
Torque control active
No
Yes
6030
03
Speed control active
No
Yes
6040
05
Speed controller I component held
No
Yes
6040
06
Speed controller I component set
No
Yes
6040
07
Torq limit reached
No
Yes
6060
08
Upper torque limit active
No
Yes
-
09
Lower torque limit active
No
Yes
-
10
Droop enabled
No
Yes
6030
11
Speed setpoint limited
No
Yes
6030
12
Ramp-function generator set
No
Yes
-
13
Sensorless operation due to a fault
No
Yes
-
r1408
CO/BO: Closed-loop control status word 3 / Control ZSW3
VECTOR (n/M)
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Data set:
-
Function diagram:
6493
P-Group:
Control
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
Current ctrl act
not active
active
-
01
Id control, I-component limiting
not active
active
-
03
Voltage limiting
not active
active
-
10
Speed adaptation, limiting
not active
active
-
11
Speed adaptation, speed deviation
In tolerance
Out tolerance
6719
12
Motor stalled
No
Yes
6719
p1416[0...n]
Speed setpoint filter 1 time constant / n_set_filt 1 T
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
5020,
6030
P-Group:
Control
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0.00 [ms]
5000.00 [ms]
0.00 [ms]
p1428[0...n]
Speed pre-control balancing deadtime / n_pre bal t_dead
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
5030,
6031
P-Group:
Control
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0.0 2.0
0.0
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...