Description:
Sets the signal source for the actual value of the technology controller.
Description:
Sets the time constant for the actual value filter (PT1) of the technology controller.
Description:
Displays the smoothed actual value after the filter (PT1) of the technology controller
Description:
Displays the error (system deviation) between the setpoint and actual value of the technology controller.
Dependency:
Refer to: p2263
Description:
Sets the time constant for the differentiation (D component) of the technology controller.
Note:
p2274 = 0: Differentiation is disabled.
Description:
Sets the proportional gain (P component) of the technology controller.
p2264[0...n]
CI: Technology controller actual value / Tec_ctr act val
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Unsigned32
Data set:
CDS
Function diagram:
7958
P-Group:
Technology
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p2265
Technology controller actual value filter time constant / Tec_ctr act T
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
7958
P-Group:
Technology
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.00 [s]
60.00 [s]
0.00 [s]
r2266
CO: Technology controller actual value after filter / Tec_ctr act a. flt
VECTOR (Tech ctrl)
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
7958
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
r2273
CO: Technology controller error / Tec_ctr error
VECTOR (Tech ctrl)
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
7958
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2274
Technology controller differentiation, time constant / Tec_ctr T diff
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
7958
P-Group:
Technology
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
60.000 [s]
0.000 [s]
p2280
Technology controller proportional gain / Tec_ctr Kp
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
7958
P-Group:
Technology
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0.000 1000.000
1.000
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...