Description:
Sets the highest possible speed/velocity.
The value in p1082 is calculated, during the commissioning phase, dependent on the motor and drive unit and can
only be equal to or less than the value in p0322 (maximum motor speed).
Dependency:
If a sinusoidal filter (p0230 = 3) is parameterized as output filter, then the maximum speed is limited corresponding
to the maximum permissible filter output frequency (refer to the filter data sheet).
Refer to: p0115, p0230, r0313, p0322, r0336
Note:
The parameter applies for both motor directions.
Description:
Sets the maximum speed/velocity for the positive direction.
Description:
Displays the effective positive speed/velocity limit.
Description:
Sets the signal source for the speed/velocity limit of the positive direction.
Description:
Sets the speed/velocity limit for the negative direction (of rotation).
p1082[0...n]
Maximum speed / Maximum speed
VECTOR
Can be changed:
C2, T
Access level:
1
Data type:
Floating Point
Data set:
DDS
Function diagram:
3050,
3060, 3070, 5300
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.000 [1/min]
210000.000 [1/min]
1500.000 [1/min]
p1083[0...n]
CO: Speed limit in positive direction of rotation / n_limit pos
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
3050
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.000 [1/min]
210000.000 [1/min]
210000.000 [1/min]
r1084
Speed limit positive effective / n_limit pos eff
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
3050,
5030, 5210, 6640, 8010
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
- [1/min]
- [1/min]
- [1/min]
p1085[0...n]
CI: Speed limit in positive direction of rotation / n_limit pos
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
3050
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1083[0]
p1086[0...n]
CO: Speed limit negative direction of rotation / n_limit neg
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
3050
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
-210000.000 [1/min]
0.000 [1/min]
-210000.000 [1/min]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...