Parameters
Parameter list
1-308
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the setpoint for the input voltage in the simulation mode of the analog inputs of terminal board 30 (TB30).
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Dependency:
The simulation of an analog input is selected using p4097.
Refer to: p4097
Note:
AI: Analog input
This parameter is not saved when data is backed-up (p0971, p0977).
Description:
Sets the setpoint for the input value in simulation mode of the analog inputs of terminal module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The simulation of an analog input is selected using p4097.
If AI x is parameterized as voltage input (p4056), then the setpoint is a voltage in V.
If AI x is parameterized as current input (p4056), then the setpoint is current in mA.
Refer to: p4056, p4097
Note:
AI: Analog input
This parameter is not saved when data is backed-up (p0971, p0977).
Description:
Sets the sampling time for the inputs and outputs of the terminal board 30 (TB30).
Index:
[0] = Digital inputs/outputs
[1] = Analog inputs
[2] = Analog outputs
Dependency:
The parameter can only be modified for p0009 = 3, 29.
The sampling times can only be set as an integer multiple of the basic sampling time (p0110, p0111).
Refer to: p0009, p0110, p0111
Note:
The modified sampling time is not effective until the drive unit is powered-up again.
p4098[0...1]
TB30 analog inputs simulation mode setpoint / TB30 AI sim setpt
TB30
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
9104
P-Group:
Terminals
Units group:
VOLTAGE_AC_PP
Unit selection:
-
Min Max
Factory
setting
-11.000 [V]
11.000 [V]
0.000 [V]
p4098[0...1]
TM31 analog inputs simulation mode setpoint / TM31 AI sim setpt
TM31
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
9566,
9568
P-Group:
Terminals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
-20.000 20.000
0.000
p4099[0...2]
TB30 inputs/outputs, sampling time / TB30 I/O t_sample
TB30
Can be changed:
C1
Access level:
4
Data type:
Floating Point
Data set:
-
Function diagram:
9100
P-Group:
Commands
Units group:
TIME_M6
Unit selection:
-
Min Max
Factory
setting
0.00 [µs]
5000.00 [µs]
[0] 4000.00 [µs]
[1] 4000.00 [µs]
[2] 4000.00 [µs]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...