Parameter list
Parameters
1-141
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the minimum speed/velocity for the motorized potentiometer.
Note:
This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
Description:
Sets the signal source to invert the maximum or minimum speed/velocity for the motorized potentiometer.
Dependency:
Refer to: p1037, p1038
Note:
The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
Description:
Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has
been powered-up.
Dependency:
Only effective if p1030.0 = 0.
Refer to: p1030
Description:
Sets the signal source to change over from manual to automatic when using a motorized potentiometer.
In the manual mode, the setpoint is changed using two signals - raise and lower. In the automatic mode, the set-
point must be interconnected via a connector input.
Dependency:
Refer to: p1030, p1035, p1036, p1042
Note:
The effectiveness of the internal ramp-function generator can be set in automatic mode.
p1038[0...n]
Motorized potentiometer, minimum speed / Mop n_min
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
3020
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
-210000.000 [1/min]
210000.000 [1/min]
0.000 [1/min]
p1039[0...n]
BI: Motorized potentiometer, inversion / Mop inversion
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
3020
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p1040[0...n]
Motorized potentiometer, starting value / Mop start value
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
3020
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
-210000.000 [1/min]
210000.000 [1/min]
0.000 [1/min]
p1041[0...n]
BI: Motorized potentiometer, manual/automatic / Mop manual/auto
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
3020
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...