Parameters
Parameter list
1-44
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
Topology coding: abcd efgh hex
a = number of active line modules
b = number of motor modules
c = number of motors
d = number of encoders (or the line supply voltage sensing for active line modules)
e = number of additional encoders (or the line supply voltage sensing for active line modules)
f = number of terminal modules
g = number of terminal boards
h = reserved
if the value 0 is displayed in all indices, then components are not detected via DRIVE-CLiQ.
If a value F hex occurs at a position of the coding (abcd efgh hex), then an overflow has occurred.
Description:
Sets the device target topology in coded form (see r0098). The setting is made during commissioning.
Index:
[0] = DRIVE-CLiQ socket X100
[1] = DRIVE-CLiQ socket X101
[2] = DRIVE-CLiQ socket X102
[3] = DRIVE-CLiQ socket X103
[4] = DRIVE-CLiQ socket X104
[5] = DRIVE-CLiQ socket X105
Dependency:
The parameter can only be written into for p0097 = 0.
To perform an automatic device configuration run, an index of the device target topology must be set to the value of
the device actual topology in r0098 for acknowledgement. An index of the device actual topology with a value other
than 0 must be selected.
Refer to: p0097, r0098
Refer to: A01330
Note:
The parameter can only be set to the values 0, the value of the actual device topology, the value of the actual
device target topology and FFFFFFFF hex.
If the value 0 is displayed in all of the indices, then the system has still not be commissioned.
The value FFFFFFFF hex indicates that the topology was not generated by the automatic device configuration but
was commissioned using the commissioning software (e.g. using parameter download).
Description:
Defines whether the motor and drive converter power settings (e.g. rated motor power - p0307) are expressed in
[kW] or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
The following applies for IEC drives: The power factor (p0308) should be parameterized.
The following applies for NEMA drives: The efficiency (p0308) should be parameterized.
Values:
0:
IEC motor [50 Hz / kW]
1:
NEMA motor [60 Hz / hp]
Dependency:
If p0100 is changed, all of the rated motor parameters are reset.
Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0336, r0337, p1800
p0099[0...5]
Device target topology / Device_target topo
CU
Can be changed:
C1
Access level:
1
Data type:
Unsigned32
Data set:
-
Function diagram:
-
P-Group:
Topology
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p0100
IEC/NEMA mot stds / IEC/NEMA mot stds
VECTOR
Can be changed:
C2
Access level:
1
Data type:
Integer16
Data set:
-
Function diagram:
-
P-Group:
Drive converter
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
0
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...