Faults and Alarms
List of faults and alarms
3-528
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Cause:
When detecting the actual topology, a ring-type connection was detected.
Fault value (r0949, hexadecimal):
Low word: Preliminary component number of a component included in the ring
Byte 3: Component class
Byte 4: Connection number
Example:
Fault value = 33751339 dec = 203012B hex
Byte 4 = 02 hex = 2 dec, byte 3 = 03 hex = 3 dec, low word = 012B hex = 299 dec
Component class:
1: Control unit
2: Motor module
3: Line module
4: Sensor module (SM)
5: Voltage sensing module (VSM)
6: Terminal module (TM)
7: DMC20, repeater
8: CX32
49: DRIVE-CLiQ components (non-listed components)
50: Option slot (e.g. terminal board 30)
60: Encoder (e.g. EnDat)
70: Motor with DRIVE-CLiQ
Component type:
Precise designation within a component class (e.g. "SMC20").
Connection number:
Consecutive numbers, starting from zero, of the appropriate connection or slote (e.g. DRIVE-CLiQ connection X100
on the control unit has the connection number 0).
Remedy:
Output the fault value and remove the specified connection.
F01380
Topology: Actual topology, defective EEPROM
Reaction:
NONE
Acknowledge:
power on
Cause:
When detecting the actual topology, a component with a defective EEPROM was detected.
Fault value (r0949, hexadecimal):
Low word:
Preliminary component number of the defective components.
Remedy:
Output the fault value and remove the defected component.
A01381
Topology: Comparison shows power module shifted
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a power module in the actual topology that has been shifted with respect to
the target topology.
Alarm value (r2124, hexadecimal):
Byte 1: Component number of the component shifted in the target topology.
The connection in the actual topology where the shifted component was detected, is described in bytes 2, 3 and 4.
Byte 2: Component class
Byte 3: component number
Byte 4: Connection number
Note:
Component class and connection number are described in F01375.
The drive system run-up is stopped. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting the topologies:
- undo the change to the actual topology by changing-over the DRIVE-CLiQ cables.
- commissioning software: Go online, upload the drive unit, adapt the topology offline and download the modified
project.
- automatically remove the topology error (p9904).
A01382
Topology: Comparison shows sensor module shifted
Reaction:
NONE
Acknowledge:
NONE
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...