Parameter list
Parameters
1-201
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the P gain of the field-weakening controller.
Description:
Sets the integral-action time of the field-weakening controller.
Description:
Displays the output of the field weakening controller. The value is referred to the rated motor flux.
Description:
Displays the effective flux setpoint. The value is referred to the rated motor flux.
Description:
Sets the static torque setpoint for sensorless vector control (SLVC). This parameter is entered as a percentage
referred to the rated motor torque (r0333).
For sensorless closed-loop vector control, when the motor model is shut down, an absolute current is impressed.
p1610 represents the maximum load that occurs at a constant setpoint speed.
Notice:
p1610 should always be set to at least 10 % higher than the maximum steady-state load that can occur.
Note:
For p1610 = 0%, a current setpoint is calculated that corresponds to the no-load case (rated magnetizing current).
For p1610 = 100 %, a current setpoint is calculated that corresponds to the rated motor torque.
p1594[0...n]
Field-weakening controller, P gain / Field_ctrl Kp
VECTOR (n/M)
Can be changed:
C2, U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
6724
P-Group:
Control
Units group:
GAIN_VOLTAGE_CTRL
Unit selection:
-
Min Max
Factory
setting
0.00 [A/V]
1000.00 [A/V]
0.00 [A/V]
p1596[0...n]
Field weakening controller integral-action time / Field_ctrl Tn
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
6723,
6724
P-Group:
Control
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
10 [ms]
10000 [ms]
50 [ms]
r1597
Field weakening controller output / Field_ctrl output
VECTOR (n/M)
Can be changed:
-
Access level:
4
Data type:
Floating Point
Data set:
-
Function diagram:
6723
P-Group:
Control
Units group:
FLUX_RELATIVE
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
r1598
CO: Total flux setpoint / Flux setpt total
VECTOR (n/M)
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
6714,
6723
P-Group:
Control
Units group:
FLUX_RELATIVE
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
p1610[0...n]
Torque setpoint static (SLVC) / M_set static
VECTOR (n/M)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
-
P-Group:
Control
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
0.0 [%]
200.0 [%]
50.0 [%]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...