Parameters
Parameter list
1-120
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
For drives with closed-loop speed control (p1300 = 20, 21), the following applies:
Bit 0 = 0: OFF1 (braking with the ramp-function generator, then pulse cancellation and power-on inhibit)
For drives with closed-loop torque control (p1300 = 22, 23), the following applies:
Bit 0 = 0: Immediate pulse cancellation
For drives with closed-loop torque control (activated using p1501), the following applies:
Bit 0 = 0: No dedicated braking response, but pulse cancellation when standstill is detected (p1226, p1227)
For drives with closed-loop speed/torque control, the following applies:
Bit 0 = 0/1: ON (pulses can be enabled)
For active infeed units, the following applies:
Bit 0 = 0: OFF1 (reduce Vdc along the ramp, then pulse cancellation and pre-charging contactor/line contactor
open)
Bit 0 = 0/1: ON (pre-charging contactor/line contactor closed, pulses can be enabled)
For passive infeed units (basic line module) the following applies:
Bit 0 = 0: OFF1 (pre-charging contactor/line contactor open)
Bit 0 = 0/1: ON (pre-charging contactor/line contactor closed)
r0863.1 of a drive can also be selected as signal source.
Description:
Sets the signal source for the 1st OC/OFF2.
The AND logic operation of the 1st OC/OFF2 and 2nd OC/OFF2 results in control word 1, bit 1 (OC/OFF2).
Note:
For drives, the following applies:
Bit 1 = 0: OFF2 (immediate pulse cancellation and power-on inhibit)
Bit 1 = 1: No OFF2 (enable is possible)
For infeed units, the following applies:
Bit 1 = 0: OFF2 (immediate pulse cancellation for active infeed units, pre-charging contactor/line contactor open
and power-on inhibit)
Bit 1 = 1: No OFF2 (enable is possible)
OC: Operating condition
Description:
Sets the signal source for the 2nd OC/OFF2.
The AND logic operation of the 1st OC/OFF2 and 2nd OC/OFF2 results in control word 1, bit 1 (OC/OFF2).
Note:
For drives, the following applies:
Bit 1 = 0: OFF2 (immediate pulse cancellation and power-on inhibit)
Bit 1 = 1: No OFF2 (enable is possible)
For infeed units, the following applies:
Bit 1 = 0: OFF2 (immediate pulse cancellation for active infeed units, pre-charging contactor/line contactor open
and power-on inhibit)
Bit 1 = 1: No OFF2 (enable is possible)
OC: Operating condition
p0844[0...n]
BI: 1. OFF2 / 1. OFF2
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2501,
8920
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
p0845[0...n]
BI: 2. OFF2 / 2. OFF2
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2501,
8920
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...