Parameter list
Parameters
1-221
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Displays phase correction currents as well as the drive converter phase currents
Index:
[0] = Harmonics, phase U
[1] = Harmonics, phase V
[2] = Harmonics, phase W
[3] = Meas. val. phase U
[4] = Meas. val. phase V
[5] = Meas. val. phase W
Description:
Displays the phase correction voltages and and the drive converter phase voltages
Index:
[0] = Harmonics, phase U
[1] = Harmonics, phase V
[2] = Harmonics, phase W
[3] = Meas. val. phase U
[4] = Meas. val. phase V
[5] = Meas. val. phase W
Description:
Sets the motor data identification and speed/velocity controller optimization.
p1900 = 0:
Function inhibited.
p1900 = 1: (sets p1910 = 1 and p1960 = 0, 1, 2 depending on the setting of p1300)
When the drive enable signals are present, a motor data identification routine is carried-out with the next power-on
command. Current flows through the motor which means that it can align itself by up to a quarter of a revolution.
With the subsequent power-on command, the speed/velocity controller is optimized by making various measure-
ments with different motor speeds/velocities.
p1900 = 2: (sets p1910 = 1)
When the drive enable signals are present, a motor data identification routine is carried-out with the next power-on
command. Current flows through the motor which means that it can align itself by up to a quarter of a revolution.
Values:
0:
Inhibited
1:
Identification of motor data and controller optimization with the motor rotating
2:
Motor data identification
Dependency:
Refer to: p1300, p1910, p1960
Refer to: A07980, A07981, A07982, A07983, A07984, A07985, F07986, A07987, A07988, F07990, A07991
Notice:
In order to permanently accept the determined settings they must be saved in a non-volatile fashion (p0971,
p0977).
r1848[0...5]
Actual value correction, phase currents / ActVal_corr I_corr
VECTOR
Can be changed:
-
Access level:
4
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
r1849[0...5]
Actual value correction, phase voltages / ActVal_corr V_corr
VECTOR
Can be changed:
-
Access level:
4
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
p1900
Motor data identification routine and speed controller optimization / MotID and n_opt
VECTOR
Can be changed:
C2, T
Access level:
1
Data type:
Integer16
Data set:
-
Function diagram:
-
P-Group:
Motor identification
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 2
2
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...