![Siemens SINAMICS G Скачать руководство пользователя страница 519](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180519.webp)
List of faults and alarms
Faults and Alarms
3-519
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
F01043
Fatal error when downloading a project
Reaction:
OFF2 (OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A fatal error was detected when downloading a project using the commissioning (start-up) software.
Fault value (r0949, decimal):
1: Device status cannot be changed to Device Download (drive object ON?).
2: Drive object ID incorrect
3: A drive object that has already been deleted is deleted again.
4: Deletes drive object that has already been registered for generation.
5: Deletes a drive object that no longer exists.
6: Generating an undeleted drive object that already existed.
7: Regeneration of a drive object already registered for generation.
8: Maximum number of drive objects that can be generated exceeded.
9: Error while generating a device drive object.
10: Error while generating target topology parameters (p9902 and p9903).
11: Error when generating a drive object (global component).
12: Error when generating a drive object (drive component).
13: Unknown drive object type.
14: Drive status cannot be changed to Drive Download.
15: Drive status cannot be changed to Ready (p0947 and p0949).
16: Device status cannot be changed to Ready.
17: It is not possible to download the topology. The component wiring should be checked, taking into account the
various messages/signals.
18: A new download is only possible if the factory settings are re-established for the drive unit.
19: The slot for the option module has been configured several times (e.g. CAN and COMM BOARD)
20: The configuration is inconsistent (e.g. CAN for control unit, however no CAN configured for drive objects - active
line module, servo or vector).
Remedy:
- use the actual version of the commissioning software.
- modify the offline project and carry-out a new download (e.g. compare the number of drive objects, motor, encoder,
power module in the offline project and at the drive).
- change the drive system (is a drive rotating or is there a message/signal?).
- carefully note any other messages/signals and remove their cause.
F01044
CU CompactFlash: Message description incorrect
Reaction:
OFF2
Acknowledge:
power on
Cause:
An error was detected when loading the message descriptions (FDxxxyyy.ACX) saved on the CompactFlash Card.
Fault value (r0949, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Replace the CompactFlash Card.
A01045
CU CompactFlash: Configuration data invalid
Reaction:
NONE
Acknowledge:
NONE
Cause:
An invalid data type was detected when evaluating parameter files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxxyyy.ACX
or CCxxxyyy.ACX, saved on the CompactFlash Card.
Alarm value (r2124, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit. Operation without any restric-
tions is then possible.
After downloading the project, save the parameterization in STARTER using the function "Copy RAM to ROM" or
with p0977 = 1 so that the incorrect parameter files are overwritten on the CompactFlash Card.
A01046 (F)
CU CompactFlash: Configuration data invalid
Reaction:
NONE
Acknowledge:
NONE
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...