Parameter list
Parameters
1-177
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
The purpose of slip compensation is to maintain a constant motor speed regardless of the applied load. The fact
that the motor speed decreases with increasing load is a typical characteristic of induction motors.
For synchronous motors, this effect does not occur and the parameter has no effect in this case.
Description:
Sets the limit value for slip compensation in [%] referred to r0330 (motor rated slip).
Description:
Displays the actual compensated slip [%] referred to r0330 (rated motor slip).
Dependency:
p1335 > 0 %: Slip compensation active.
Refer to: p1335
Description:
Sets the controller gain for resonance damping for V/f control.
Dependency:
Refer to: p1300, p1339
Note:
The resonance damping function dampens active current oscillations that frequency occur under no-load condi-
tions.
The resonance damping is active in a range of approximately 5 ... 70 % of the rated motor frequency (p0310).
Description:
Sets the filter time constant of the controller for resonance damping with V/f control.
Dependency:
Refer to: p1300, p1338
p1336[0...n]
Slip compensation limit value / Slip comp lim val
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
6310
P-Group:
V/f control
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
0.00 [%]
600.00 [%]
250.00 [%]
r1337
Actual slip compensation / Slip comp act.val.
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
6310
P-Group:
V/f control
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
p1338[0...n]
V/f mode resonance damping gain / Uf Res_damp gain
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
1690,
6310
P-Group:
V/f control
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0.00 100.00
0.00
p1339[0...n]
V/f mode resonance damping filter time constant / Uf Res_damp T
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
6310
P-Group:
V/f control
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
1.00 [ms]
1000.00 [ms]
20.00 [ms]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...