Parameter list
Parameters
1-171
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the output limit for the Vdc controller (DC link voltage controller).
Description:
Activates/de-activates the automatic sensing of the switch-in level for the Vdc_max controller.
Values:
0:
Automatic detection disabled
1:
Automatic detection enabled
Description:
Sets the time threshold for the Vdc_min controller (kinetic buffering). If this value is exceeded a fault is output; the
required response can be parameterized .
Prerequisite: p1296 = 1.
Description:
Sets the response for the Vdc_min controller (kinetic buffering).
Values:
0:
Buffer Vdc up to possible failure with undervoltage., n<p1257 -> F7405
1:
Buffer Vdc up to possible failure with undervoltage, n<p1257 -> F7405, t>p1255 -> F7406
Description:
Sets the speed threshold for the Vdc-min controller (kinetic buffering). If this value is exceeded a fault is output; the
required response can be parameterized .
p1293[0...n]
Vdc controller output limit (V/f) / Vdc_ctrl outp_lim
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
6320
P-Group:
Functions
Units group:
FREQUENCY
Unit selection:
-
Min Max
Factory
setting
0.0 [Hz]
600.0 [Hz]
10.0 [Hz]
p1294
Vdc_max controller automatic detection ON signal level (V/f) / Vdc_max SenseOnLev
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Data set:
-
Function diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
1
p1295[0...n]
Vdc_min controller time threshold (V/f) / Vdc_min t_thresh
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
-
P-Group:
Functions
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.000 [s]
10000.000 [s]
0.000 [s]
p1296[0...n]
Vdc_min controller response (kinetic buffering) (V/f / Vdc_min response
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Data set:
DDS
Function diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
0
p1297[0...n]
Vdc_min controller speed threshold (V/f) / Vdc_min n_thresh
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
-
P-Group:
Functions
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.0 [1/min]
210000.0 [1/min]
50.0 [1/min]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...