Parameters
Parameter list
1-216
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Displays the power-on slip frequency for the Lh adaptation of the induction motor.
Description:
Sets the integral action time for the kT adaptation of the motor model for the synchronous motor.
Description:
Displays the correction value for the kT adaptation of the motor model for the synchronous motor.
Description:
Sets the drive converter switching frequency.
This parameter is preset to the rated converter value when the drive is first commissioned.
Dependency:
The switching frequency can only be changed in an integer ratio to the current controller sampling rate (p0115[0]).
The minimum pulse frequency is half the value of the current controller sampling rate (current controller frequency).
If a sinusoidal filter is parameterized as output filter (p0230 = 3), then the pulse frequency cannot be changed below
the minimum value required for the filter.
Refer to: p0110, p0111, p0112, p0115, p0230
Note:
The maximum possible pulse frequency is also determined by the power module being used.
When the pulse frequency is increased, depending on the particular power module, the maximum output current
can be reduced (de-rating, refer to r0067).
Description:
Displays the actual converter switching frequency.
r1792
Motor model IM Lh adaptation switch-on slip / MotMod Lh fslip
VECTOR (n/M)
Can be changed:
-
Access level:
4
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Control
Units group:
FREQUENCY
Unit selection:
-
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
p1795[0...n]
Motor model PESM kT adaptation integral action time / MotMod kT Tn
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
6731
P-Group:
Control
Units group:
TIME_M3
Unit selection:
p0528
Min Max
Factory
setting
10 [ms]
10000 [ms]
100 [ms]
r1797
Motor model PESM kT adaptation correction value / MotMod kT corr
VECTOR (n/M)
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
6731
P-Group:
Control
Units group:
TORQUE_PER_CURR
Unit selection:
-
Min Max
Factory
setting
- [Nm/A]
- [Nm/A]
- [Nm/A]
p1800[0...n]
Pulse frequency / Pulse frequency
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
-
P-Group:
Modulation
Units group:
FREQUENCY_P3
Unit selection:
-
Min Max
Factory
setting
1.000 [kHz]
16.000 [kHz]
4.000 [kHz]
r1801
Actual pulse frequency / Pulse freq actual
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Displays, signals
Units group:
FREQUENCY_P3
Unit selection:
-
Min Max
Factory
setting
- [kHz]
- [kHz]
- [kHz]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...