Parameters
Parameter list
1-310
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the fault/alarm threshold for the temperature evaluation of terminal module 31 (TM31).
Temperature actual value > p4102[0] --> alarm A35211 is output.
Temperature actual value > p4102[1] --> fault F35207 is output.
Index:
[0] = Alarm threshold
[1] = Fault threshold
Dependency:
Refer to: r4104
Warning!
Fault F35207 only causes the drive to be shut down if there is at least one BICO interconnection between the drive
and TM31.
Note:
The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
A value > 250 °C deactivates the alarm or fault.
Description:
Displays the status for the temperature evaluation of terminal module 31 (TM31).
This displays as to whether the temperature actual value has exceeded the fault/alarm threshold.
Dependency:
Refer to: p4102
Description:
Displays the actual temperature value of the temperature evaluation of terminal module 31 (TM31).
Dependency:
For sensor type PTC (p4100 = 1), the following applies:
- below the nominal response temperature, r4105 = -50°C.
- above the nominal response temperature, r4105 = 199.9 °C.
For sensor type KTY84-130 (p4100 = 2), the following applies:
- the displayed value corresponds to the temperature actual value.
Refer to: p4100
Note:
The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
For an invalid temperature actual value, (e.g. a short-circuit at the sensor input), r4105 = -300 °C is displayed.
p4102[0...1]
TM31 temperature evaluation fault/alarm threshold / TM31 temp thresh
TM31
Can be changed:
T
Access level:
1
Data type:
Integer16
Data set:
-
Function diagram:
9576
P-Group:
-
Units group:
TEMPERATURE
Unit selection:
-
Min Max
Factory
setting
-48 [°C]
251 [°C]
[0] 100 [°C]
[1] 120 [°C]
r4104
BO: TM31 temperature evaluation, status / TM31 temp status
TM31
Can be changed:
-
Access level:
1
Data type:
Unsigned16
Data set:
-
Function diagram:
1840,
9576
P-Group:
Terminals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
Temperature alarm threshold exceeded
No
Yes
-
01
Temperature fault threshold exceeded
No
Yes
-
r4105
CO: TM31 temperature evaluation, actual value / TM31 temp actValue
TM31
Can be changed:
-
Access level:
1
Data type:
Floating Point
Data set:
-
Function diagram:
1840,
9576
P-Group:
Terminals
Units group:
TEMPERATURE
Unit selection:
-
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...