![Siemens SINAMICS G Скачать руководство пользователя страница 121](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180121.webp)
Parameter list
Parameters
1-121
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the signal source for the 1st OC/OFF3.
The AND logic operation of the 1st OC/OFF3 and 2nd OC/OFF3 results in control word 1, bit 2 (OC/OFF3).
Note:
Bit 2 = 0: OFF3 (braking along the OFF3 ramp (p1135), then pulse cancellation and power-on inhibit)
Bit 2 = 1: No OFF3 (enable is possible)
OC: Operating condition
Description:
Sets the signal source for the 2nd OC/OFF3.
The AND logic operation of the 1st OC/OFF3 and 2nd OC/OFF3 results in control word 1, bit 2 (OC/OFF3).
Note:
Bit 2 = 0: OFF3 (braking along the OFF3 ramp (p1135), then pulse cancellation and power-on inhibit)
Bit 2 = 1: No OFF3 (enable is possible)
OC: Operating condition
Description:
Sets the signal source for control word 1 bit 3 (enable operation)
Note:
Bit 3 = 0: Inhibit operation (cancel pulses)
Bit 3 = 1: Enable operation (pulses can be enabled)
Description:
Sets the signal source for control word 1 bit 10 (PLC control).
Note:
Bit 10 = 0: PLC has no master control
Bit 10 = 1: Master ctrl by PLC
p0848[0...n]
BI: 1. OFF3 / 1. OFF3
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2501
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
p0849[0...n]
BI: 2. OFF3 / 2. OFF3
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2501
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
p0852[0...n]
BI: Enable operation / Enable operation
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2442,
2443, 2501, 8920
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
p0854[0...n]
BI: Master ctrl by PLC / Master ctrl by PLC
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2501,
2442, 2443, 8920
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...