Parameter list
Parameters
1-263
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Configuration word for messages and monitoring functions.
Dependency:
Refer to: r2197
Refer to: A07903
Note:
Re bit 00:
Alarm A07903 is output when the bit is set with p2197.7 = 0 (n_set <> n_act).
Description:
Sets the hysteresis speed/velocity (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency:
Refer to: p2161, r2197, r2199
Description:
Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
Ramp-up/ramp-down completed (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency:
Refer to: r2197, r2198, r2199
Description:
Sets the time constant of the PT1 element to smooth the speed / velocity actual value. The smoothed actual
speed/velocity is compared with the threshold values and is only used for messages and signals.
Dependency:
Refer to: r2169
p2149[0...n]
Monitoring, configuration / Monit config
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Unsigned16
Data set:
DDS
Function diagram:
8010
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0000 bin
0001 bin
0000 bin
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
Enable alarm A07903
No
Yes
8010
p2150[0...n]
Hysteresis speed 3 / n_hysteresis 3
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
8010
P-Group:
Messages
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.00 [1/min]
300.00 [1/min]
2.00 [1/min]
p2151[0...n]
CI: Speed setpoint for messages/signals / n_set for msg
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
8010
P-Group:
Messages
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
1170[0]
p2153[0...n]
Speed actual value filter time constant / n_act_filt T
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
8010
P-Group:
Messages
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0 [ms]
1000000 [ms]
0 [ms]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...