Parameter list
Parameters
1-277
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency:
Refer to: r2250
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2248
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2247
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p1030.2) the ramp-down is correspondingly extended.
Description:
Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency:
Refer to: r2245
r2245
CO: Technology controller motorized potentiometer setpoint before RFG / Tec_ctr
mop b. RFG
VECTOR (Tech ctrl)
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
7954
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2247[0...n]
Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
7954
P-Group:
Technology
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.0 [s]
1000.0 [s]
10.0 [s]
p2248[0...n]
Technology controller motorized potentiometer ramp-down time / Tec_ctrMop
t_rdown
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
7954
P-Group:
Technology
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.0 [s]
1000.0 [s]
10.0 [s]
r2250
CO: Technology controller motorized potentiometer setpoint after RFG / Tec_ctr mop
a. RFG
VECTOR (Tech ctrl)
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
7954
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...