![Siemens SINAMICS G Скачать руководство пользователя страница 271](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180271.webp)
Parameter list
Parameters
1-271
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the signal source to switch-in/switch-out the technology controller.
The technology controller is switched-in with a 1 signal.
Description:
Sets the value for fixed value 1 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Description:
Sets the value for fixed value 2 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Description:
Sets the value for fixed value 3 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Description:
Sets the value for fixed value 4 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
p2200[0...n]
BI: Technology controller enable / Tec_ctr enable
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Unsigned32
Data set:
CDS
Function diagram:
7958
P-Group:
Technology
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p2201[0...n]
CO: Technology controller, fixed value 1 / Tec_ctr fix val 1
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
7950
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
0.00 [%]
p2202[0...n]
CO: Technology controller, fixed value 2 / Tec_ctr fix val 2
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
7950
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
10.00 [%]
p2203[0...n]
CO: Technology controller, fixed value 3 / Tec_ctr fix val 3
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
7950
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
20.00 [%]
p2204[0...n]
CO: Technology controller, fixed value 4 / Tec_ctr fix val 4
VECTOR (Tech ctrl)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
7950
P-Group:
Technology
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
30.00 [%]
Содержание SINAMICS G
Страница 1: ...List Manual 12 2004 Edition sinamics SINAMICS G ...
Страница 2: ......
Страница 8: ...Preface Preface 8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 680: ...List of Abbreviations Abbreviations 680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 686: ...References References 686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...
Страница 696: ...Index Index 696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual Edition 12 2004 ...